Water Quality Analysis (Daily)

Daily lab analysis is the primary method for validating plant performance and regulatory compliance.

Routine Bench Tests

Operators must perform the following bench tests every 4 hours.

Parameter Target Range Critical Limit Method
pH (Raw) 6.8 - 7.2 N/A Electrometric
pH (Finished) 8.0 - 8.5 < 7.5 Electrometric
Chlorine (Free) 1.8 - 2.2 mg/L < 1.5 mg/L DPD Colorimetric
Turbidity (Clearwell) < 0.10 NTU > 0.30 NTU Nephelometric
Fluoride 0.6 - 0.8 mg/L > 2.0 mg/L SPADNS

Sampling Locations

  1. Raw Water: Sample tap located on the incoming 48" line (Pre-Aeration).
  2. Settled Water: Sample from the flume exiting the sedimentation basins.
  3. Entry Point (EP): Finished water tap in the lab (Representing water entering distribution).

!!! danger "Critical Violation" If Entry Point Free Chlorine drops below 0.2 mg/L, you must immediately notify the Chief Operator and start the Low Chlorine Emergency Protocol.